Factory Price 113.58kw Cooling Capacity Air Cooled Chiller For Electroplating Industry
Main Features
1. Suitable for the building with 200-10000m2.
2. Air conditioner system with cold and heat source unity, no boiler room needed, more suitable for simultaneous
heating and cooling needs of users.
3. Install it outdoor, do not need refrigerator room, eliminating the need for refrigeration room, saving construction
investment.
4. The first nergy utilization rate is up to 90%, saving energy consumption, greatly reducing the cost of the user.
5. No cooling tower needed, at the same time, eliminating the need of water pump and pipe system, reducing the
cost of extra equipment.
6. No cooling water system power consumption, no cooling water loss, more suitable for water shortage areas.
Technical Parameters :
Model No. |
RHP-40A |
Refrigeration Capacity |
113.58KW (32.29Ton,97675Kcal/h) |
Temp. Control Range |
5ºC ~ 35ºC |
Power Supply |
380V-3Phase-50Hz |
Total Power Consumption |
37.1kw |
Refrigerant |
Type |
R407C |
Control |
Thermal Expansion Valve |
Compressor |
Brand |
Panasonic |
Type |
Hermetic Scroll |
Power |
15kw x 2 |
Condenser |
Type |
Efficient copper aluminum Fin & Low Noise Fan |
Cooling Air Flow |
40000m3/h |
Fan Power |
0.6kw x 6 |
Evaporator |
Type |
Tank Coils |
Chilled Water |
19.53m3/h |
Tank Volume |
610L |
Inlet/Outlet Pipe |
Dia.3" |
Water Pump |
Power |
4kw |
Max Flow Rate |
36m3/h |
Lift |
25m |
Controller |
PLC |
Protector Device |
Compressor overheating protection, over current protection, high and low pressure protection traffic protection, phase sequence/phase loss protection, low level protection, frost protection over temperature protection |
Size |
L2360 x W1360 x H2020 mm |
Weight |
1200kg |
Work Condition
- Above cooling capacity is based on Chilled Water Inlet=12°C & Outlet=7°C, Ambient Temp.=35°C .
- Power Supplier Options: 220V-3Phase-50Hz/60Hz, 380V-3Phase-50Hz/60Hz, 415V-3Phase-50Hz/60Hz .
- Refrigerant Options: R407C, R134a, R404a .
Work Principle
Structure Drawing
Package & Shipping
(1) Use standard export plywood case with forklift truck feet, easy to load and unload .
(2) 5-7 days to finish the production after receiving the deposit .
(3) Shipping by LCL or FCL .
After-sales service:
(1) 12 months quality warranty since the date of delivery .
(2) Free of charge to replace new chillers if quality problems.
(3) Cost price to buy extra parts with Chillers from Ruihai if needed.
(4) 24 hours online service by e-mail, WhatsApp, Skype or Telephone Calling.
(5) Installation Video to help installation even send engineer to customer's jobsite
if needed.
Necessary info to Quote
1.What is your cooling capacity ?_____ Kcal/hr or _____KW ?
2. What's your power supply? For example: 220V-50Hz-1N (N=Phase )
3.What refrigerant type do you require? R134a or R407c ?
4. What's your ambient temperature? And what is your chiller inlet and
outlet water temperature ?
5. Which industry do you use the chiller in ?